Orinox Chill Series is equipped with a choice of two compressor,axial fan and Shell & tube evaporator, the chillers are also supplied with a water pump, making them compatible with water-glycolmixtures, and a storage tank that ensures precise temperature control, even when process thermal loads fluctuate significantly. With cooling capacities ranging up to 382 kW, these chillers canmeet a wide variety of customer needs.

Cooling Capacity: 41,24 kW - 382 kW
Refrigerant: R-410A
Compressor: Dual compressors
Cooling Type: Air-cooled
Applications: Industrial cooling, process cooling,
HVAC systems

Durable cabinet

High-efficiency condenser

Easy-service access design

Teknik Özellikler

Orinox Chill Teknik Özellikleri

Orinox chill 2 Series 

PERFORMANCE VALUES A (Tin: 15 / Tout: 10 / T ambient: 25) / REFRIGERANT: R-410A 

MODEL

 

RF-2F1PH27

RF-3F1ST210

RF-4F1ST212

RF-2F2ST215

RF-2F2ST220

RF-6F2ST225

RF-4F2ST230

RF-6F2ST240

RF-6F2ST250

COOLING CAPACITY

Kw

46

66,8

76,36

100

133

163

204

263

322,6

kcal/h

39.514

57.381

65.593

85.900

114.178

139.673

175.236

225.573

277.113

COMPRESSOR QUANTITY

QTY

2

2

2

2

2

2

2

2

2

COMPRESSOR TYPE

TYPE

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

COMPRESSOR POWER

kw

8,6

12,8

14,68

17,72

24

29

36,84

46,46

57,7

CAPACITY STEP

N

2

2

2

2

6

6

6

6

6

ABSORBED POWER

kw

12,8

17,6

20

25,22

31,5

36,1

45,14

62,96

74,2

EER

EER

3,59

3,80

3,82

3,96

4,22

4,50

4,52

4,2

4,35

POWER SUPPLY

V/Ph/Hz

380- 400V-3ph-50Hz

PROTECTION CLASS

 IP 

IP54

FAN QUANTITY

QTY

2

3

4

2

2

6

4

6

6

FAN SIZE

mm

500Ø

500Ø

500Ø

800Ø

800Ø

500Ø

800Ø

800Ø

800Ø

WATER FLOW

m3/h

7,90

11,48

13,12

17,2

22,8

27,9

35,0

45,1

55,4

EVAPORATOR TYPE

ST / PH

Plate exchanger

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

PERFORMANCE VALUES B (Tin: 15 / Tout: 10 / T ambient: 35)/ REFRIGERANT: R-410A 

MODEL

 

RF-2F1PH27

RF-3F1ST210

RF-4F1ST212

RF-2F2ST215

RF-2F2ST220

RF-6F2ST225

RF-4F2ST230

RF-4F2ST240

RF-6F2ST250

COOLING CAPACITY

Kw

40

58,94

68

87

117

143

180

232

284,8

kcal/h

34.360

50.629

58.412

74.475

100.417

122.837

154.620

198.944

244.643

COMPRESSOR QUANTITY

QTY

2

2

2

2

2

2

2

2

2

COMPRESSOR TYPE

TYPE

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

COMPRESSOR POWER

kw

10,52

15,6

18

22,28

30,54

36,48

46,38

58,4

72,88

CAPACITY STEP

N

2

2

2

2

6

6

6

6

6

ABSORBED POWER

kw

14,72

20,4

23,4

29,78

38

43,58

54,68

70,9

89,38

EER

EER

2,72

2,89

2,91

2,92

3,07

3,28

3,29

3,27

3,2

POWER SUPPLY

V/Ph/Hz

380- 400V-3ph-50Hz

PROTECTION CLASS

 IP 

IP54

FAN QUANTITY

QTY

2

3

4

2

2

6

4

4

6

FAN SIZE

mm

500Ø

500Ø

500Ø

800Ø

800Ø

500Ø

800Ø

800Ø

800Ø

WATER FLOW

m3/h

6,87

10,13

11,68

14,9

20,1

24,6

30,9

39,8

48,9

EVAPORATOR TYPE

ST / PH

Plate exchanger

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

PERFORMANCE VALUES C (Tin: 15 / Tout: 10 / T ambient: 40)/ REFRIGERANT: R-410A 

MODEL

 

RF-2F1PH27

RF-3F1ST210

RF-4F1ST212

RF-2F2ST215

RF-2F2ST220

RF-6F2ST225

RF-4F2ST230

RF-4F2ST240

RF-6F2ST250

COOLING CAPACITY

Kw

37,26

54,68

63,28

80

108

132,38

166

215

264,4

kcal/h

32.006

46.970

54.358

68.720

92.772

113.714

142.250

184.513

227.120

COMPRESSOR QUANTITY

QTY

2

2

2

2

2

2

2

2

2

COMPRESSOR TYPE

TYPE

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

SCROLL

COMPRESSOR POWER

kw

11,6

17,24

20

24,84

34

40,7

51,68

64,8

81,2

CAPACITY STEP

N

2

2

2

2

6

6

6

6

6

ABSORBED POWER

kw

15,8

22,04

25,4

32,34

41,5

47,8

59,98

77,3

97,7

EER

EER

2,36

2,48

2,49

2,47

2,6

2,77

2,76

2,78

2,71

POWER SUPPLY

V/Ph/Hz

380- 400V-3ph-50Hz

PROTECTION CLASS

 IP 

IP54

FAN QUANTITY

QTY

2

3

4

2

2

6

4

4

6

FAN SIZE

mm

500Ø

500Ø

500Ø

800Ø

800Ø

500Ø

800Ø

800Ø

800Ø

WATER FLOW

m3/h

6,40

9,39

10,87

13,7

18,6

22,7

28,5

36,9

45,4

EVAPORATOR TYPE

ST / PH

Plate exchanger

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

shell & tube

Water pump

Yes / No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

TANK CAPACITY

LT

180LT

200LT

200LT

260LT

260LT

260LT

360LT

360LT

500LT

WATER CONNECTION

Inch

1 1/4"

1 1/2"

1 1/2"

2"

2 1/2"

2 1/2"

3"

4"

4"

DIMENSIONS

 

 

 

 

 

 

L (LENGTH)

mm

1730

2600

2600

2750

2750

2750

2925

2925

4100

W (WIDTH)

mm

1010

1010

1010

1350

1350

1350

2255

2255

2255

H (HEIGHT)

mm

1600

1500

1500

2500

2500

2300

2400

2400

2400

WEIGHT

kg

380kg

580KG

580KG

950kg

1000kg

1000kg

1600kg

1600kg

2000kg

*AREF SOĞUTMA reserves the right to change models, capacities and dimensions without prior notice.

Technical Overview

About Air-Cooled Chiller

Air-cooled chiller systems transfer heat to the outside air through condenser fans. With practical installation, low maintenance needs and a structure suited to outdoor applications, they are widely used in commercial and industrial facilities.

An air-cooled chiller is a cooling unit that transfers heat to the ambient air and is commonly used in commercial and industrial applications. Air-cooled chillers cool water for use in air conditioning, industrial processes, and a variety of other applications.

An air-cooled chiller uses a refrigerant to cool water. The cooling process takes place through a cycle in which the water is cooled in the evaporator and the heat is transferred to the air in the condenser. Fans dissipate the heat into the ambient air, cooling the system.

It is easier to install and lower in cost. Since it consumes no water, it does not require a water source. It requires less maintenance because there are no issues related to water treatment or water piping. Because it can be used outdoors, it saves indoor floor space.

Its operating efficiency depends on the outdoor air temperature; performance may drop in hot weather. The noise level is high because the fans run continuously. The cooling capacity is generally lower than that of water-cooled chillers.

The fans and condensers need to be cleaned regularly. It is important to check and replace the filters frequently. The refrigerant levels and system pressures should be checked regularly. The electrical connections and motors need to be inspected regularly.

Air conditioning systems in commercial buildings Industrial process cooling Data centers Hospitals and laboratories Food and beverage industry Plastic injection molding facilities Extrusion facilities Metal and steel processing facilities

Cooling capacity and energy efficiency The environmental conditions of the installation site (air temperature, humidity, etc.) Ease of maintenance and service Noise level Initial investment cost and operating costs